ELMOR S.A.
ul. Spadochroniarzy 20
80-298 Gdańsk
POLAND
tel.: +48 (58) 785-36-70
fax: +48 (58) 762-93-19
e-mail: elmor@elmor.com.pl
TABULA switchgears and controlgears
Our offer » Low Voltage distribution and control equipment up to 1kV » TABULA switchgears and controlgears
TABULA switchgears and controlgears
The system of switchgears and controlgears TABULA has been based on a three-dimensional module 126 mm in all three directions: height, width and depth.
All components e.g.: main elements of housings like doors, insulation barriers, montage plates and bus-bars are based on this dimension.
TABULA system enables among others:
- Building of the switchgear consisting of any amount of the modules,
- Building of the switchgear at the angle of 90° using typical elements of this system,
- Building of the switchgears and controlgears divided into compartments acc. to any chosen form,
- Obtention max. rated continuous currents at min. material consumption,
- Very high withstand to short-circuit currents,
- Quick assembly and simple ways of connections and attachments,
- High protection degree for persons i.e. protection against accidental touch of alive parts and protection against electric arc effects,
- Install in all network systems defined in PN-91/E-05009 and IEC-346 designated as the systems of type TN, TT and IT,
- High resistance to aggressive industrial environment.
![]() |
![]() |
All main construction elements besides painted doors and shields are made of Aluzinc, a material of high corrosion resistance. Aluzinc is a high quality steel sheet covered with alu-zinc coat consisting of 55% aluminium, 43,4% zinc and 1,6% silicon.
Shields and doors are made of high quality phosphate treated steel sheet.
The switchgear with withdrawable units of the system TABULA gives the possibility to carry out functional test of auxiliary circuits assuring safety insulation clearance in the main circuit.
TABULA system compiles the requirements contained in PN-IEC 439-1+AC.
![]() |
![]() |
Technical data:
Insulation rated voltage | 1000 V |
Rated frequency | 50¸60 Hz |
Continuous rated current of | |
horizontal bus-bars | 250÷7800 A |
vertical bus-bars | 225÷1600 A |
Rated short-time withstand current (1 sec.) of | |
horizontal bus-bars | 115 kA |
vertical bus-bars | 91 kA |
Rated peak withstand current of | |
horizontal bus-bars | 253 kA |
vertical bus-bars | 200 kA |
Protection degree | IP20÷IP54 |
Dielectric test voltage | 3500 V/min |
Tests and certficates:
KEMA | Holland | ![]() |
ASTA | England | |
DEMKO | Denmark | |
SETI | Finland | |
ELEKTRONIKCENTRALEN | Denmark | |
SYDNEY CITY COUNCIL | Australia | |
NEFI | Norway |
Attachments